Tableau pression–température R404A

Pression et température de saturation du R404A : convertissez température en pression ou pression en température, et consultez le tableau complet.

Fluide frigorigène

Classe de sécurité
A1
GWP (AR4)
3 922
Glissement de température
≈ 0.7 K

Liquide (bulle)

5,09 barg

6,10 bar a · 73,8 psig

Vapeur (rosée)

4,99 barg

6,01 bar a · 72,4 psig

Type: Mélange quasi azéotropeClasse de sécurité: A1GWP (AR4): 3 922Glissement de température: ≈ 0,7 KPoint critique: 72,1 °C · 37,3 bar

R404A — Tableau pression–température

°C°FLiquide (bulle) bar aLiquide (bulle) bargVapeur (rosée) bar aVapeur (rosée) bargVapeur (rosée) psig
-40-40,01,350,341,310,304,3
-38-36,41,480,461,430,426,1
-36-32,81,610,601,560,558
-34-29,21,760,741,710,6910
-32-25,61,910,901,860,8412,2
-30-22,02,081,062,021,0114,6
-28-18,42,251,242,191,1817,1
-26-14,82,441,422,381,3619,8
-24-11,22,631,622,571,5622,6
-22-7,62,841,832,781,7625,6
-20-4,03,072,053,001,9928,8
-18-0,43,302,293,232,2232,2
-163,23,552,543,482,4735,8
-146,83,822,803,742,7339,5
-1210,44,103,084,023,0043,6
-1014,04,393,384,313,3047,8
-817,64,703,694,613,6052,2
-621,25,024,014,943,9256,9
-424,85,374,355,274,2661,8
-228,45,724,715,634,6267
032,06,105,096,014,9972,4
235,66,505,486,405,3878,1
439,26,915,906,815,7984
642,87,346,337,236,2290,2
846,47,806,787,686,6796,8
1050,08,277,268,167,14103,6
1253,68,777,758,657,64110,7
1457,29,288,279,168,15118,2
1660,89,828,819,708,69126
1864,410,389,3710,269,25134,2
2068,010,979,9610,859,84142,7
2271,611,5810,5711,4610,44151,5
2475,212,2211,2112,0911,08160,6
2678,812,8811,8712,7511,73170,2
2882,413,5712,5613,4312,42180,1
3086,014,2913,2814,1413,13190,4
3289,615,0314,0214,8813,87201,2
3493,215,8014,7915,6614,64212,4
3696,816,6015,5916,4615,44224
38100,417,4316,4217,2916,27236
40104,018,2917,2818,1517,14248,5
42107,619,1918,1719,0518,03261,5
44111,220,1219,1019,9818,96275
46114,821,0820,0620,9419,92289
48118,422,0721,0621,9320,92303,4
50122,023,1022,0922,9621,95318,3
52125,624,1823,1624,0423,02333,9
54129,225,2924,2825,1524,14350
56132,826,4425,4326,3025,28366,7
58136,427,6326,6127,4826,47383,9
60140,028,8527,8428,7127,70401,7

bar a = absolue (bar a) · barg = relative (barg) (bar a − 1,013)

Tous les fluides