Tableau pression–température R449A

Pression et température de saturation du R449A : convertissez température en pression ou pression en température, et consultez le tableau complet.

Fluide frigorigène

Classe de sécurité
A1
GWP (AR4)
1 397
Glissement de température
≈ 4.5 K

Liquide (bulle)

5,10 barg

6,12 bar a · 74,0 psig

Vapeur (rosée)

4,12 barg

5,14 bar a · 59,8 psig

Type: Mélange zéotropeClasse de sécurité: A1GWP (AR4): 1 397Glissement de température: ≈ 4,5 KPoint critique: 81,5 °C · 44,5 bar

R449A — Tableau pression–température

°C°FLiquide (bulle) bar aLiquide (bulle) bargVapeur (rosée) bar aVapeur (rosée) bargVapeur (rosée) psig
-40-40,01,320,311,010,000
-38-36,41,450,441,110,101,4
-36-32,81,580,571,220,213
-34-29,21,730,711,340,334,7
-32-25,61,880,871,470,456,6
-30-22,02,051,031,610,598,6
-28-18,42,221,211,750,7410,7
-26-14,82,411,401,910,9013
-24-11,22,611,602,081,0715,5
-22-7,62,821,812,261,2518,1
-20-4,03,052,032,451,4420,9
-18-0,43,282,272,661,6423,8
-163,23,542,522,871,8627
-146,83,802,793,102,0930,3
-1210,44,093,073,352,3333,8
-1014,04,393,373,612,5937,6
-817,64,703,683,882,8741,6
-621,25,024,014,173,1545,7
-424,85,374,364,473,4650,2
-228,45,734,724,803,7854,9
032,06,125,105,144,1259,8
235,66,525,505,494,4865
439,26,945,925,874,8570,4
642,87,386,376,265,2576,1
846,47,846,836,685,6782,2
1050,08,337,317,126,1088,5
1253,68,837,827,576,5695,1
1457,29,368,348,057,04102,1
1660,89,918,898,557,54109,3
1864,410,489,479,088,06116,9
2068,011,0810,079,638,61124,9
2271,611,7010,6910,209,19133,2
2475,212,3511,3310,809,79141,9
2678,813,0212,0111,4210,41151
2882,413,7212,7112,0811,07160,5
3086,014,4513,4412,7611,75170,4
3289,615,2114,1913,4712,45180,6
3493,215,9914,9814,2113,19191,3
3696,816,8115,7914,9713,96202,5
38100,417,6516,6415,7714,76214
40104,018,5317,5216,6015,59226,1
42107,619,4418,4317,4716,46238,7
44111,220,3819,3718,3717,36251,8
46114,821,3520,3419,3118,30265,4
48118,422,3621,3520,2819,27279,5
50122,023,4022,3921,2920,28294,1
52125,624,4823,4622,3521,33309,4
54129,225,5924,5823,4422,43325,3
56132,826,7425,7324,5723,56341,7
58136,427,9326,9125,7524,73358,7
60140,029,1528,1426,9625,95376,3

bar a = absolue (bar a) · barg = relative (barg) (bar a − 1,013)