R134a pressure–temperature chart

Saturation pressure and temperature of R134a: convert temperature to pressure or pressure to temperature, and see the full table.

Refrigerant

Safety class
A1
GWP (AR4)
1,430
Temperature glide
No glide

Saturation point

1.91 barg

2.93 bar a · 27.8 psig

Type: Pure substanceSafety class: A1GWP (AR4): 1,430Temperature glide: No glideCritical point: 101.1 °C · 40.6 bar

R134a — Pressure–temperature table

°C°Fbar abargpsig
-50-58.00.29-0.72-10.4
-48-54.40.33-0.68-9.9
-46-50.80.37-0.64-9.3
-44-47.20.41-0.60-8.7
-42-43.60.46-0.55-8
-40-40.00.51-0.50-7.3
-38-36.40.57-0.45-6.5
-36-32.80.63-0.38-5.6
-34-29.20.69-0.32-4.6
-32-25.60.77-0.25-3.6
-30-22.00.84-0.17-2.5
-28-18.40.93-0.09-1.3
-26-14.81.020.000
-24-11.21.110.101.4
-22-7.61.220.202.9
-20-4.01.330.314.6
-18-0.41.450.436.3
-163.21.570.568.1
-146.81.710.6910.1
-1210.41.850.8412.2
-1014.02.010.9914.4
-817.62.171.1616.8
-621.22.341.3319.3
-424.82.531.5121.9
-228.42.721.7124.8
032.02.931.9127.8
235.63.152.1330.9
439.23.382.3634.3
642.83.622.6137.8
846.43.882.8641.5
1050.04.153.1345.4
1253.64.433.4249.5
1457.24.733.7153.9
1660.85.044.0358.4
1864.45.374.3663.2
2068.05.724.7068.2
2271.66.085.0673.5
2475.26.465.4478.9
2678.86.855.8484.7
2882.47.276.2590.7
3086.07.706.6997
3289.68.157.14103.6
3493.28.637.61110.4
3696.89.128.10117.5
38100.49.638.62125
40104.010.179.15132.7
42107.610.729.71140.8
44111.211.3010.29149.2
46114.811.9010.89157.9
48118.412.5311.52167
50122.013.1812.17176.4
52125.613.8512.84186.2
54129.214.5613.54196.4
56132.815.2814.27207
58136.416.0415.02217.9
60140.016.8215.80229.2
62143.617.6316.62241
64147.218.4717.46253.2
66150.819.3418.33265.8
68154.420.2419.22278.8
70158.021.1720.15292.3

bar a = absolute (bar a) · barg = gauge (barg) (bar a − 1,013)

All refrigerants

Need a definitive selection for your project?Send us your calculation; our technical team selects the evaporator and condensing unit for your room conditions and prepares a quote.Request a quote