R744 pressure–temperature chart

Saturation pressure and temperature of R744: convert temperature to pressure or pressure to temperature, and see the full table.

Refrigerant

Safety class
A1
GWP (AR4)
1
Temperature glide
No glide

Saturation point

33.84 barg

34.85 bar a · 490.8 psig

Type: Pure substanceSafety class: A1GWP (AR4): 1Temperature glide: No glideCritical point: 31.0 °C · 73.8 bar

R744 — Pressure–temperature table

°C°Fbar abargpsig
-54-65.25.784.7769.1
-52-61.66.295.2776.5
-50-58.06.825.8184.3
-48-54.47.396.3892.5
-46-50.88.006.99101.3
-44-47.28.647.63110.7
-42-43.69.338.31120.6
-40-40.010.059.04131.1
-38-36.410.819.79142.1
-36-32.811.6110.59153.7
-34-29.212.4511.44165.9
-32-25.613.3412.33178.8
-30-22.014.2813.27192.4
-28-18.415.2614.25206.6
-26-14.816.2915.28221.6
-24-11.217.3716.36237.3
-22-7.618.5117.50253.8
-20-4.019.7018.69271
-18-0.420.9419.93289
-163.222.2421.23307.9
-146.823.6022.58327.5
-1210.425.0124.00348.1
-1014.026.4925.48369.5
-817.628.0327.02391.8
-621.229.6328.62415.1
-424.831.3130.29439.3
-228.433.0432.03464.6
032.034.8533.84490.8
235.636.7435.72518.1
439.238.6937.68546.5
642.840.7339.71576
846.442.8341.82606.6
1050.045.0244.01638.3
1253.647.3146.29671.4
1457.249.6848.66705.8
1660.852.1351.12741.4
1864.454.6753.65778.2
2068.057.2956.28816.2
2271.660.0459.03856.1
2475.262.8861.87897.4
2678.865.8564.84940.4
2882.468.9467.93985.3
3086.072.1471.131,031.6

bar a = absolute (bar a) · barg = gauge (barg) (bar a − 1,013)

All refrigerants

Need a definitive selection for your project?Send us your calculation; our technical team selects the evaporator and condensing unit for your room conditions and prepares a quote.Request a quote