R449A pressure–temperature chart

Saturation pressure and temperature of R449A: convert temperature to pressure or pressure to temperature, and see the full table.

Refrigerant

Safety class
A1
GWP (AR4)
1,397
Temperature glide
≈ 4.5 K

Liquid (bubble)

5.10 barg

6.12 bar a · 74.0 psig

Vapor (dew)

4.12 barg

5.14 bar a · 59.8 psig

Type: Zeotropic blendSafety class: A1GWP (AR4): 1,397Temperature glide: ≈ 4.5 KCritical point: 81.5 °C · 44.5 bar

R449A — Pressure–temperature table

°C°FLiquid (bubble) bar aLiquid (bubble) bargVapor (dew) bar aVapor (dew) bargVapor (dew) psig
-40-40.01.320.311.010.000
-38-36.41.450.441.110.101.4
-36-32.81.580.571.220.213
-34-29.21.730.711.340.334.7
-32-25.61.880.871.470.456.6
-30-22.02.051.031.610.598.6
-28-18.42.221.211.750.7410.7
-26-14.82.411.401.910.9013
-24-11.22.611.602.081.0715.5
-22-7.62.821.812.261.2518.1
-20-4.03.052.032.451.4420.9
-18-0.43.282.272.661.6423.8
-163.23.542.522.871.8627
-146.83.802.793.102.0930.3
-1210.44.093.073.352.3333.8
-1014.04.393.373.612.5937.6
-817.64.703.683.882.8741.6
-621.25.024.014.173.1545.7
-424.85.374.364.473.4650.2
-228.45.734.724.803.7854.9
032.06.125.105.144.1259.8
235.66.525.505.494.4865
439.26.945.925.874.8570.4
642.87.386.376.265.2576.1
846.47.846.836.685.6782.2
1050.08.337.317.126.1088.5
1253.68.837.827.576.5695.1
1457.29.368.348.057.04102.1
1660.89.918.898.557.54109.3
1864.410.489.479.088.06116.9
2068.011.0810.079.638.61124.9
2271.611.7010.6910.209.19133.2
2475.212.3511.3310.809.79141.9
2678.813.0212.0111.4210.41151
2882.413.7212.7112.0811.07160.5
3086.014.4513.4412.7611.75170.4
3289.615.2114.1913.4712.45180.6
3493.215.9914.9814.2113.19191.3
3696.816.8115.7914.9713.96202.5
38100.417.6516.6415.7714.76214
40104.018.5317.5216.6015.59226.1
42107.619.4418.4317.4716.46238.7
44111.220.3819.3718.3717.36251.8
46114.821.3520.3419.3118.30265.4
48118.422.3621.3520.2819.27279.5
50122.023.4022.3921.2920.28294.1
52125.624.4823.4622.3521.33309.4
54129.225.5924.5823.4422.43325.3
56132.826.7425.7324.5723.56341.7
58136.427.9326.9125.7524.73358.7
60140.029.1528.1426.9625.95376.3

bar a = absolute (bar a) · barg = gauge (barg) (bar a − 1,013)