R717 pressure–temperature chart

Saturation pressure and temperature of R717: convert temperature to pressure or pressure to temperature, and see the full table.

Refrigerant

Safety class
B2L
GWP (AR4)
0
Temperature glide
No glide

Saturation point

3.28 barg

4.29 bar a · 47.6 psig

Type: Pure substanceSafety class: B2LGWP (AR4): 0Temperature glide: No glideCritical point: 132.3 °C · 113.3 bar

R717 — Pressure–temperature table

°C°Fbar abargpsig
-50-58.00.41-0.60-8.8
-48-54.40.46-0.55-8
-46-50.80.52-0.50-7.2
-44-47.20.58-0.44-6.3
-42-43.60.64-0.37-5.4
-40-40.00.72-0.30-4.3
-38-36.40.80-0.22-3.1
-36-32.80.88-0.13-1.9
-34-29.20.98-0.03-0.5
-32-25.61.080.071
-30-22.01.200.182.6
-28-18.41.320.304.4
-26-14.81.450.436.3
-24-11.21.590.578.3
-22-7.61.740.7310.5
-20-4.01.900.8912.9
-18-0.42.081.0615.4
-163.22.261.2518.1
-146.82.461.4521
-1210.42.681.6624.1
-1014.02.911.8927.5
-817.63.152.1431
-621.23.412.4034.8
-424.83.692.6738.8
-228.43.982.9743
032.04.293.2847.6
235.64.623.6152.4
439.24.973.9657.4
642.85.344.3362.8
846.45.744.7268.5
1050.06.155.1474.5
1253.66.595.5780.8
1457.27.046.0387.5
1660.87.536.5194.5
1864.48.047.02101.9
2068.08.577.56109.7
2271.69.148.12117.8
2475.29.728.71126.3
2678.810.349.33135.3
2882.410.999.98144.7
3086.011.6710.66154.6
3289.612.3811.36164.8
3493.213.1212.11175.6
3696.813.8912.88186.8
38100.414.7013.69198.6
40104.015.5514.54210.8
42107.616.4315.42223.6
44111.217.3516.34236.9
46114.818.3117.29250.8
48118.419.3018.29265.3
50122.020.3419.33280.3
52125.621.4120.40295.9
54129.222.5321.52312.1
56132.823.6922.68328.9
58136.424.9023.89346.4
60140.026.1525.14364.6

bar a = absolute (bar a) · barg = gauge (barg) (bar a − 1,013)