R507A pressure–temperature chart

Saturation pressure and temperature of R507A: convert temperature to pressure or pressure to temperature, and see the full table.

Refrigerant

Safety class
A1
GWP (AR4)
3,985
Temperature glide
No glide

Saturation point

5.23 barg

6.25 bar a · 75.9 psig

Type: Azeotropic blendSafety class: A1GWP (AR4): 3,985Temperature glide: No glideCritical point: 70.6 °C · 37.1 bar

R507A — Pressure–temperature table

°C°Fbar abargpsig
-40-40.01.390.375.4
-38-36.41.510.507.3
-36-32.81.650.649.3
-34-29.21.800.7911.4
-32-25.61.960.9513.7
-30-22.02.131.1216.2
-28-18.42.311.3018.8
-26-14.82.501.4921.5
-24-11.22.701.6924.5
-22-7.62.921.9027.6
-20-4.03.142.1330.9
-18-0.43.382.3734.4
-163.23.642.6338.1
-146.83.912.9042
-1210.44.193.1846.1
-1014.04.503.4850.5
-817.64.813.8055.1
-621.25.144.1359.9
-424.85.494.4865
-228.45.864.8570.3
032.06.255.2375.9
235.66.655.6481.7
439.27.076.0687.9
642.87.516.5094.3
846.47.986.96101
1050.08.467.45108
1253.68.977.95115.3
1457.29.498.48123
1660.810.059.03131
1864.410.629.61139.3
2068.011.2210.21148
2271.611.8410.83157.1
2475.212.4911.48166.5
2678.813.1712.15176.3
2882.413.8712.86186.5
3086.014.6013.59197.1
3289.615.3614.35208.1
3493.216.1515.14219.5
3696.816.9715.96231.4
38100.417.8216.81243.8
40104.018.7017.69256.5
42107.619.6218.60269.8
44111.220.5619.55283.6
46114.821.5520.53297.8
48118.422.5621.55312.5
50122.023.6122.60327.7
52125.624.7123.70343.7
54129.225.8524.84360.2
56132.827.0226.01377.3
58136.428.2427.22394.9
60140.029.4928.48413

bar a = absolute (bar a) · barg = gauge (barg) (bar a − 1,013)

All refrigerants

Need a definitive selection for your project?Send us your calculation; our technical team selects the evaporator and condensing unit for your room conditions and prepares a quote.Request a quote