R448A pressure–temperature chart

Saturation pressure and temperature of R448A: convert temperature to pressure or pressure to temperature, and see the full table.

Refrigerant

Safety class
A1
GWP (AR4)
1,387
Temperature glide
≈ 5 K

Liquid (bubble)

5.23 barg

6.24 bar a · 75.8 psig

Vapor (dew)

4.14 barg

5.16 bar a · 60.1 psig

Type: Zeotropic blendSafety class: A1GWP (AR4): 1,387Temperature glide: ≈ 5.0 KCritical point: 83.7 °C · 46.6 bar

R448A — Pressure–temperature table

°C°FLiquid (bubble) bar aLiquid (bubble) bargVapor (dew) bar aVapor (dew) bargVapor (dew) psig
-40-40.01.350.341.010.000
-38-36.41.480.471.120.101.5
-36-32.81.620.601.230.213.1
-34-29.21.760.751.350.334.8
-32-25.61.920.911.470.466.7
-30-22.02.091.081.610.608.7
-28-18.42.271.251.760.7510.8
-26-14.82.461.441.920.9013.1
-24-11.22.661.652.091.0715.6
-22-7.62.871.862.271.2518.2
-20-4.03.102.092.461.4521
-18-0.43.342.332.661.6524
-163.23.602.592.881.8727.1
-146.83.872.863.112.1030.5
-1210.44.163.143.362.3534
-1014.04.463.453.622.6137.8
-817.64.783.773.892.8841.8
-621.25.124.104.183.1746
-424.85.474.464.493.4850.4
-228.45.854.834.813.8055.1
032.06.245.235.164.1460.1
235.66.645.635.524.5165.3
439.27.076.065.904.8970.9
642.87.526.506.305.2976.7
846.47.986.976.735.7182.8
1050.08.477.467.176.1689.3
1253.68.987.977.636.6295.9
1457.29.518.508.117.10102.9
1660.810.079.058.617.60110.2
1864.410.659.639.148.13117.9
2068.011.2510.249.698.68125.9
2271.611.8810.8710.279.26134.3
2475.212.5411.5310.889.86143
2678.813.2312.2111.5110.49152.2
2882.413.9412.9312.1611.15161.7
3086.014.6813.6712.8511.84171.7
3289.615.4514.4313.5712.55182
3493.216.2415.2314.3113.30192.9
3696.817.0716.0515.0914.07204.1
38100.417.9216.9115.8914.88215.8
40104.018.8117.8016.7315.72228
42107.619.7318.7117.6116.59240.7
44111.220.6719.6618.5217.50253.9
46114.821.6620.6419.4618.45267.6
48118.422.6721.6620.4419.43281.8
50122.023.7222.7121.4620.45296.6
52125.624.8123.8022.5321.51312
54129.225.9424.9323.6322.62328.1
56132.827.1126.1024.7823.76344.7
58136.428.3227.3025.9624.95361.9
60140.029.5628.5527.1926.18379.7

bar a = absolute (bar a) · barg = gauge (barg) (bar a − 1,013)